Fire-Resistance Test Report of E1 Stress Grade Cross-Laminated Timber Assemblies

https://research.thinkwood.com/en/permalink/catalogue356
Year of Publication
2013
Topic
Fire
Material
CLT (Cross-Laminated Timber)
Application
Walls
Floors
Author
Ranger, Lindsay
Dagenais, Christian
Organization
FPInnovations
Year of Publication
2013
Country of Publication
Canada
Format
Report
Material
CLT (Cross-Laminated Timber)
Application
Walls
Floors
Topic
Fire
Keywords
National Building Code of Canada
Fire Resistance
Type X Gypsum Board
Language
English
Research Status
Complete
Summary
A series of 3 cross-laminated timber (CLT) fire-resistance tests were conducted in accordance with ULC S101 standard as required in the National Building Code of Canada. The first two tests were 3-ply wall assemblies which were 105 mm thick, one unprotected and the other protected with an intumescent coating, FLAMEBLOC® GS 200, on the exposed surface. The walls were loaded to 295 kN/m (20 250 lb./ft.). The unprotected assembly failed structurally after 32 minutes, and the protected assembly failed after 25 minutes. The third test consisted of a 175 mm thick 5-ply CLT floor assembly which used wood I-joists, resilient channels, insulation and 15.9 mm ( in.) Type X gypsum board protection. A uniform load of 5.07 kPa (106 lb./ft²) was applied. The floor assembly failed after 138 min due to integrity.